Modular Walk-In Cold Room Sizing & Installation Guide (10m²–50m²)
Practical pre-purchase engineering guide covering layout, power supply, condenser ventilation, and storage tonnage for 10m²–50m² walk-in coolers.
1. Effective Volume & Shelving Layout
A 10 m² (2.5m × 4.0m × 2.5m = 25 m³) walk-in room accommodates 4-tier 50 cm deep racks along both long walls with a 90 cm central aisle, yielding 4–5 tons of organized storage while leaving clear airflow throw beneath the ceiling evaporator.
2. Floor Levelness & Condensation Drainage
Never place an open floor drain inside a -18°C freezer room. Modular rooms up to 50 m² assemble cleanly over a level concrete slab using interlocking insulated floor panels, while evaporator defrost lines route outside via a trapped, heated drain.
3. Power Supply & Condenser Airflow Clearance
10–15 m² positive coolers can run on 220–240V single-phase, whereas 20 m²+ chambers and all -18°C freezers perform best on 380–415V 3-phase power. Ensure at least 80 cm clear airflow in front of and behind outdoor condensing units.
Frequently Asked Questions
How much electricity does a 10m² +4°C walk-in cooler consume?
With 80–100mm PUR insulation and standard door discipline, a 10m² +4°C unit averages roughly 10 to 14 kWh per 24 hours.
Request a Turnkey Cold Storage Engineering Quotation
Share your room dimensions, target temperature, and destination port or city. Our refrigeration engineers respond with detailed heat load calculations, CAD layout, and EXW/FOB/CIF pricing.
Direct Engineering Desk
Phone / WhatsApp: +90 506 689 45 82
E-mail: export@ruzgarcooling.com
HQ & Factory: Zafertepe Mah. 533 Sk. No:9/B Yağhaneler, Konak, 35250 İzmir, Turkey