Deep Freeze Cold Storage Warehouses (-18°C / -25°C)
Frozen storage warehouses (-18°C to -25°C) featuring 150–200mm panels, heated door seals, pressure relief valves, and anti-frost-heave floor engineering.
Deep freeze storage warehouses (-18°C to -25°C) operate across a 55°C–65°C thermal delta between interior storage and exterior ambient air. Even microscopic vapor leaks cause ice bridging, panel delamination, and surging kWh bills. Rüzgar Cooling manufactures zero-thermal-bridge freezer envelopes engineered for multi-decade reliability.
Mandatory Deep-Freeze Engineering Features
- 150 mm to 200 mm PUR/PIR Panels: Ultra-low U-values (0.11–0.14 W/m²K) with triple-seal joints.
- Heated Door Frames & Thresholds: Integrated perimeter heating cables prevent door gaskets from freezing shut.
- Heated Pressure Equalization Valves: Protect structural panels from rapid vacuum/overpressure spikes during door openings and defrost cycles.
- Anti-Heave Sub-Floor Protection: Prevents subsoil moisture freezing and slab buckling under large commercial freezers.
Typical Export Applications
- Frozen beef, poultry, and seafood wholesale depots
- IQF frozen French fries, vegetables, and berries warehouses
- Ice cream and frozen bakery regional distribution centers
- Bonded export cold storage hubs at seaports
Engineering Specification Sheet
| Operating Temp | -18°C / -25°C continuous storage |
|---|---|
| Panel Thickness | 150 mm (standard) / 200 mm (hot climate & -25°C) |
| Door Hardware | Heated frame + threshold + PVC strip curtain / air curtain |
| Defrost System | Electric element or energy-saving hot gas defrost |
| Personnel Safety | Internal glow-in-dark release + man-trapped alarm |
Deep Freeze Cold Storage Warehouses (-18°C / -25°C) — Export FAQ
Can I freeze warm fresh meat directly in a -18°C storage room?
No. A -18°C storage room is sized only to hold pre-frozen goods. Freezing warm products there raises room temperature, spoils adjacent stock, and forms large ice crystals. Use a -35°C/-40°C blast freezer first.
Interactive Cold Room Sizing & Cooling Load Calculator
Enter your target internal dimensions, operating temperature, and local summer ambient climate to calculate required PUR/PIR panel thickness, cooling capacity (kW / BTU/h), and FOB İzmir reference pricing.
Calculated Engineering Output
Request a Turnkey Cold Storage Engineering Quotation
Share your room dimensions, target temperature, and destination port or city. Our refrigeration engineers respond with detailed heat load calculations, CAD layout, and EXW/FOB/CIF pricing.
Direct Engineering Desk
Phone / WhatsApp: +90 506 689 45 82
E-mail: export@ruzgarcooling.com
HQ & Factory: Zafertepe Mah. 533 Sk. No:9/B Yağhaneler, Konak, 35250 İzmir, Turkey